AMB ON Plus 31 UPS Series

Download Flyer

Feature
  • True double-conversion
  • DSP technology guarantees high performance
  • Output power factor 1
  • Active power factor correction in all phases
  • 50Hz/60Hz frequency converter mode
  • Dual AC inputs
  • Emergency power off function (EPO)
  • Generator compatible
  • Supports dual AC inputs
  • Adjustable battery numbers for long-run model
  • Maintenance bypass available
  • Parallel operation up to 4 units with common battery
  • Optional isolation transformer offers full isolation and complete
    common mode noise rejection

Specification

 

MODEL                            10K(L)*                              20K(L)*
PHASE 3Ph in 1Ph out
CAPACITY 10KVA / 10KW  20KVA / 20KW
PARALLEL CAPABILITY 4
INPUT
Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range 110-300 VAC ± 3 % @ 50% load; 176-276 VAC ± 3 % @ 100% load
Frequency Range 46~54 Hz or 56~64Hz
Power Factor   ≥0.99 @ 100% Load
Harmonic Distortion (THDi) < 4% at full linear load
OUTPUT
Output Voltage 208/220/230/240 VAC (1Ph+N)
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Synchronized Range) 46~54Hz or 56~64Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≤ 2% THD (Linear Load); £ 5% THD (Non-linear Load)
Transfer Time AC Mode to Batt. Mode: Zero Inverter to Bypass: Zero
Waveform (Batt. Mode) Pure Sine wave
Overload Capability 100-110% for 60 min, 111-125% for 10 min, 126%-150% for 1 min; >150% immediately shutdown Battery Mode
BYPASS
Nominal Voltage 208/220/230/240 VAC (1Ph+N)
Voltage Range -30% ~ +20% (Adjustable)
Frequency Range (Synchronized Range) 46~54Hz or 56~64Hz
Overload Capability   > 130% 1 minute (default); continuously working until breaker protection (optional)
EFFICIENCY
AC Mode 95.5%
ECO Mode 98.5%
Battery Mode 94.5%
BATTERY
Battery Type 12V/9Ah 12V/9Ah
Numbers (10+10) pcs (16+16) pcs
Typical Recharge Time 9 hours recover to 90% capacity
Charging Current (max.) 1A (Default) 2A (Default)
Charging Voltage ±136.5 VDC ±218 VDC
Long-run Model – Battery Type Depending on the applications
Long-run Model – Numbers 16~20 pcs (Adjustable) 32~40 pcs (Adjustable)
Charging Current (max.) 1A ~ 12A (Adjustable)
Charging Voltage ±13.65V*N (N=8~10) ±13.65V*N (N=16~20)
INDICATORS LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
PHYSICAL
Standard Model – Dimension, D×W×H (mm) 630 × 250 × 826 815 × 300 × 1000
Standard Model – Net Weight (kgs) 124 207
Long-run Model – Dimension, D×W×H (mm) 630 × 250 × 826 815 × 300 × 1000
Long-run Model – Net Weight (kgs) 37 56
ENVIRONMENT
Operation Temperature 0-40°C
Operation Humidity < 95% and non-condensing
Altitude**  0 ~ 1500m at full load
Noise Level Less than 60 dB@1 Meter Less than 65 dB@1 Meter
MANAGEMENT
Smart RS-232 / USB Supports Windows® Family, Linux and MAC
Optional  SNMP Power management from SNMP manager and web browser

*If output voltage is set as 3 x 360VAC, the output power of the unit will be de-rated to 90%.

**If the UPS is installed or used in a placed where the altitude is higher than the maximum height, the output power will de-rated 1% per 100m.

*Products specifications are subjected to change without further notice.