AMB Fortress 3P/3P Series UPS 100-200kVA

Download Flyer

Feature
  • Pluggable power module design with front access to decrease MTTR, parallel redundancy capability for  power guarantee
  • Parallel operation with common battery
  • Power walk-infunction
  • Dual-mains inputs
  • Built-in 4 switches including Mains input, bypass input, output and maintenance bypass switch
  • Flexible battery configuration and adjustable charging current
  • Output power factor 1
  • Active power factor correction in all phases
  • Built-in 7″ touch LCD screen for comprehensive information
  • Emergency Power off Function(EPO)
  • Generator compatible
  • 50Hz/60Hz frequency converter mode

Specification

MODEL Fortress 3/3 100K Fortress 3/3 120K Fortress 3/3 180K Fortress 3/3 200K
CAPACITY 100KVA/100KW 120KVA/120KW 180KVA/180KW 200KVA/200KW
PHASE 3 phase in / 3 phase out 3 phase in / 3 phase out 3 phase in / 3 phase out 3 phase in / 3 phase out
PARALLEL CAPABILITY 4 4 4 4
INPUT
Voltage Range 110-300 VAC @ 50% load; 176-276 VAC @ 100% load 110-300 VAC @ 50% load; 176-276 VAC @ 100% load 110-300 VAC @ 50% load; 176-276 VAC @ 100% load 110-300 VAC @ 50% load; 176-276 VAC @ 100% load
Nominal Voltage 3 x 380/400/415 VAC (3Ph+N) 3 x 380/400/415 VAC (3Ph+N) 3 x 380/400/415 VAC (3Ph+N) 3 x 380/400/415 VAC (3Ph+N)
Frequency Range 40~70 Hz 40~70 Hz 40~70 Hz 40~70 Hz
Nominal Frequency 50/60Hz (Auto sensing) 50/60Hz (Auto sensing) 50/60Hz (Auto sensing)
Power Factor ≧ 0.99 @ 100% load ≧ 0.99 @ 100% load ≧ 0.99 @ 100% load ≧ 0.99 @ 100% load
Harmonic Distortion (THDi) <4% @ 100% load <4% @ 100% load <4% @ 100% load <4% @ 100% load
OUTPUT
Nominal Frequency 50/60Hz 50/60Hz 50/60Hz
Overload Capability ≦ 110% for 1 hour, 111% ~ 125% for 10 mins, 126%~150% for 1 min and >150% for 200ms ≦ 110% for 1 hour, 111% ~ 125% for 10 mins, 126%~150% for 1 min and >150% for 200ms ≦ 110% for 1 hour, 111% ~ 125% for 10 mins, 126%~150% for 1 min and >150% for 200ms ≦ 110% for 1 hour, 111% ~ 125% for 10 mins, 126%~150% for 1 min and >150% for 200ms
Voltage Regulation (Steady state) ≦± 1% Typical (balanced load)
≦± 2% Typical (unbalanced load)
≦± 1% Typical (balanced load)
≦± 2% Typical (unbalanced load)
≦± 1% Typical (balanced load)
≦± 2% Typical (unbalanced load)
≦± 1% Typical (balanced load)
≦± 2% Typical (unbalanced load)
Nominal Voltage 3 x 380/400/415 VAC (3Ph+N) 3 x 380/400/415 VAC (3Ph+N) 3 x 380/400/415 VAC (3Ph+N) 3 x 380/400/415 VAC (3Ph+N)
Harmonic Distortion ≦2% THD (Linear Load)
≦4% THD (Non-linear Load)
≦2% THD (Linear Load)
≦4% THD (Non-linear Load)
≦2% THD (Linear Load)
≦4% THD (Non-linear Load)
Frequency Range (Synchronized range) 46Hz ~ 54Hz or 56Hz ~ 64Hz 46Hz ~ 54Hz or 56Hz ~ 64Hz 46Hz ~ 54Hz or 56Hz ~ 64Hz
EFFICIENCY
Battery Mode 94.5% 94.5% 94.5%
ECO Mode 98.5% 98.5% 98.5%
AC Mode 95.5% 95.5% 95.5% 95.5%
BYPASS
Overload Capability ≦ 110% for 1 hour, 111% ~ 125% for 10 mins, 126%~150% for 1 min and >150% for 200ms ≦ 110% for 1 hour, 111% ~ 125% for 10 mins, 126%~150% for 1 min and >150% for 200ms ≦ 110% for 1 hour, 111% ~ 125% for 10 mins, 126%~150% for 1 min and >150% for 200ms ≦ 110% for 1 hour, 111% ~ 125% for 10 mins, 126%~150% for 1 min and >150% for 200ms
Nominal Voltage 3 x 380/400/415 VAC (3Ph+N) 3 x 380/400/415 VAC (3Ph+N) 3 x 380/400/415 VAC (3Ph+N) 3 x 380/400/415 VAC (3Ph+N)
Voltage Range -30% ~ +20% -30% ~ +20% -30% ~ +20% -30% ~ +20%
Frequency Range 46Hz ~ 54Hz or 56Hz ~ 64Hz 46Hz ~ 54Hz or 56Hz ~ 64Hz 46Hz ~ 54Hz or 56Hz ~ 64Hz 46Hz ~ 54Hz or 56Hz ~ 64Hz
ENVIRONMENT
Altitude <1000m for Nominal power <1000m for Nominal power <1000m for Nominal power <1000m for Nominal power
Operation Temperature 0 ~ 55℃ 0 ~ 55℃ 0 ~ 55℃ 0 ~ 55℃
Relative Humidity 0 ~ 95% non-condensing 0 ~ 95% non-condensing 0 ~ 95% non-condensing 0 ~ 95% non-condensing
PHYSICAL
Net Weight (kgs) 169 169 249 249
IP Protection IP 20 IP 20 IP 20 IP 20
Dimensions, D x W x H(mm) 1000 x 430 x 1200 1000 x 430 x 1200 1000 x 600 x 1200 1000 x 600 x 1200
MANAGEMENT
Optional SNMP Power management from SNMP manager and web browser Power management from SNMP manager and web browser Power management from SNMP manager and web browser Power management from SNMP manager and web browser
RS-232/USB Supports Windows family, Linux and MAC Supports Windows family, Linux and MAC Supports Windows family, Linux and MAC Power management from SNMP manager and web browser
STANDARDS
Safety IEC/EN 62040-1 IEC/EN 62040-1 IEC/EN 62040-1 IEC/EN 62040-1
EMC IEC/EN 62040-2 Category C3 IEC/EN 62040-2 Category C3 IEC/EN 62040-2 Category C3 IEC/EN 62040-2 Category C3
BATTERY / CHARGER
Nominal Voltage +/- 192V ~ +/- 240V (Selectable) +/- 192V ~ +/- 240V (Selectable) +/- 192V ~ +/- 240V (Selectable) +/- 192V ~ +/- 240V (Selectable)
Maximum Voltage +/- 240V (12V x 40 Pcs) +/- 240V (12V x 40 Pcs) +/- 240V (12V x 40 Pcs) +/- 240V (12V x 40 Pcs)
Minimum Voltage +/- 192V (12V x 32 Pcs) +/- 192V (12V x 32 Pcs) +/- 192V (12V x 32 Pcs) +/- 192V (12V x 32 Pcs)
Floating Charge Voltage 2.28V / Cell (2.25 ~2.33 Selectable) 2.28V / Cell (2.25 ~2.33 Selectable) 2.28V / Cell (2.25 ~2.33 Selectable) 2.28V / Cell (2.25 ~2.33 Selectable)
Boost Charging Voltage 2.35V/Cell 2.35V/Cell 2.35V/Cell 2.35V/Cell
Temperature Compensation Yes Yes Yes
Maximum Charging Current 24A (Adjustable) 36A (Adjustable) 54A (Adjustable) 54A (Adjustable)

 