Model: AMB-ON-PLUS-1000-RT
Specification
Phase:Â Single phase with ground
Capacity: 1000 VA / 1000 W
Input
       Nominal Voltage: 100/110/115/120/127 VAC or 200/208/220/230/240 VAC
       Voltage range: 55-150 VAC ¹ 5% or 110-300 VAC ¹ 5% @ 50% load
80-150 VAC Âą 5% or 160-300 VAC Âą 5% @ 100% load
       Nominal Frequency: 50Hz/60Hz
       Frequency Range: 40-70Hz
       Power Factor: âĨ 0.99 @ nominal voltage (100% load)
       Harmonic Distortion (THDi): âĪ 5% @ nominal input voltage
Output
       Output Voltage(Batt. mode): 100*/110*/115*/120/127 VAC or 200*/208*/220/230/240 VAC
       AC Voltage Regulation (Batt. Mode): ¹ 1 %
       Frequency Range (Synchronized Range): 57 ~ 63 Hz or 47 ~ 53 Hz
       Frequency Range (Batt. Mode): 60Hz ¹ 0.1Hz or 50 Hz ¹ 0.1Hz
       Harmonic Distortion: âĪ 2 % THD (Linear Load) ; âĪ 4 % THD (Non-linear Load)
       Waveform: Pure Sinewave
       THDv: âĪ 3% @ linear load, âĪ5%@non-linear load
       Current Crest Ratio: 3:1 (max.)
       Transfer Time: 0 for AC Mode to Batt. Mode, 4 ms (Typical) for Inverter to Bypass
Efficiency
       AC Mode: âĨ 89% @ full charged battery
       Battery Mode: âĨ 88%
       ECO Mode: âĨ 96% @ full charged battery
Battery
        Model 1000L
        Type: 12 V/ 9 Ah
        Total Battery Quantity: 2
        Recharge Time: 3 hours recover to 95% capacity for internal battery@ 2A charging current
        Charging Voltage: 27.4 VDC ¹ 1%
        Charging Current:Â
100/110/115/120 /127 VAC models: default 2A, max. 8A adjustable
200/208/220/230/240 VAC models: default 2A, max. 12A adjustable
Indicators
        LCD Display: UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault condition
Alarm:
      Battery Mode: Sounding every 5 seconds
      Low Battery: Sounding every 2 seconds
      Overload: Sounding every seconds
      Fault: Continuously sounding
Physical
       Dimension (W x H x D) (mm): 410 x 438 x 88
       Net weight (without battery) Kgs: 6.6
       Net weight (with built in battery) Kgs: 11.6
Environment
       Operating Humidity: 20-90 % RH @ 0- 40°C (non-condensing)
       Noise Level: Less than 50dB @ 1 Meter
Â
Management
       Smart RS-232/USB: Supports Windows ÂŪ 2000/2003/XP/Vista/2008/7/8/10, Linux and MAC
       Optional SNMP: Power management from SNMP manager and web browser
       Power Management Software: Yes
Standard
       EMC/safety: EMC EN62040-2 C2 for CE models
Note: All specifications are subject to change without notice