Model: AMB-ON-PLUS-10000-RT
Specification
Phase:Â Single phase with ground
Capacity:10000 VA / 10000 W
Input
       Nominal Voltage: 100/110/115/120/127 VAC or 200/208/220/230/240 VAC
       Voltage range: 55-150 VAC ¹ 5% or 110-300 VAC ¹ 5% @ 50% load
80-150 VAC Âą 5% or 160-300 VAC Âą 5% @ 100% load
       Nominal Frequency: 50Hz/60Hz
       Frequency Range: 40-70Hz
       Power Factor: âĨ 0.99 @ nominal voltage (100% load)
       Harmonic Distortion (THDi): âĪ 5% @ nominal input voltage
Output
       Output Voltage(Batt. mode): 208*/220/230/240 VAC
       AC Voltage Regulation (Batt. Mode): ¹ 1 %
       Frequency Range (Synchronized Range): 46~54 Hz â 50Hz / 56~64 Hz â 60Hz
       Frequency Range (Batt. Mode): 50 Hz ¹ 0.1 Hz or 60 Hz ¹ 0.1 Hz
       Harmonic Distortion:âĪ1% THD (Linear Load), âĪ 4% THD (Non-linear Load)
       Waveform: Pure Sinewave
       THDv: âĪ 3% @ linear load, âĪ5%@non-linear load
       Current Crest Ratio: 3:1 (max.)
       Transfer Time: 0 for AC Mode to Batt. Mode, 0 for for Inverter to Bypass
 Overload.
AC Mode: 100%~110%: 10minã 110%~130%: 1minã>130% : 1sec
Battery Mode: 100%~110%: 30secã 110%~130%: 1minã>130% : 1sec
Efficiency
       AC Mode: âĨ 94% @ full charged battery
       Battery Mode: âĨ 92%
       ECO Mode: âĨ 98.5% @ full charged battery
Battery
        Model 10000L
Standard Model.
        Type: 12 V/ 9 AhÂ
        Total Battery Quantity:16Â
Type: 12 V/ 9 AhÂ
Total Battery Quantity:20
        Recharge Time: 9 hours recover to 90% capacity for internal battery@ 2A charging current
        Charging Voltage: 218.4 VDC ¹ 1%
Charging Voltage: 273 VDC Âą 1%
        Charging Current: 1.0 A
 Long-run Model.
Type: Depending on applications
Total Battery Quantity: 16-20**
 Charging Voltage: (13.65VDC x battery number) ¹ 1%
 Charging Current: 4.0 A
Indicators
        LCD Display: UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault condition
Alarm:
      Battery Mode: Sounding every 4 seconds
      Low Battery: Sounding every secondÂ
      Overload: Sounding twice every second
      Fault: Continuously sounding
Physical
Standard Model.
       Dimension (W x H x D) (mm): UPS Unit: 610x438x88 [2U] Battery Pack:715x438x88 [2U]
       Net weight: UPS Unit: 20
Battery Pack: 53
Dimension (W x H x D) (mm): UPS Unit: 610x438x88 [2U] Battery Pack:600x438x133 [3U]
       Net weight: UPS Unit: 20
Battery Pack: 63
Environment
       Operating Humidity: 20-90 % RH @ 0- 40°C (non-condensing)
       Noise Level: Less than 58dB @ 1 Meter
Â
Management
       Smart RS-232/USB: Supports Windows ÂŪ 2000/2003/XP/Vista/2008/7/8/10, Linux and MAC
       Optional SNMP: Power management from SNMP manager and web browser
       Power Management Software: Yes
     Â
Note: All specifications are subject to change without notice