AMB-ON-PLUS-30000 (L)*

Download Flyer

Key Features

  • True double-conversion
  • Output power factor 1
  • Output voltage regulation < 1%
  • 50Hz/60Hz frequency converter mode
  • Programmable power management outlets
  • Hot swappable battery design
  • ECO mode energy saving
  • Provides over voltage cut-off protection and surge immunity by MOV for full time equipment protection
  • High power factor charger up to 8A/12A capacity with very low ripple current when charging battery
  • Low input THDi to reduce power system pollution
  • Adjustable charging current via LCD panel
  • Optional HID Power Device USB Port
Category: Tags: ,

Model: AMB-ON-PLUS-30000 (L)*

Specification

Phase: 3-phase in / 3-phase out

Capacity:30KVA /30KW

PARALLEL CAPABILITY: up to 6 units in paralle

 

Input

              Nominal Voltage:3 x 380/400/415 VAC (3Ph+N)

              Voltage range:-30% ~ +20%

              Frequency Range:40~70 Hz

              Power Factor:@ 0.99 @ 100% Load

               Harmonic Distortion (THDi):< 3% at full linear load

 

Output

              Output Voltage(Batt. mode):3 x 360*/380/400/415 VAC (3Ph+N)/ 208*/220/230/240VAC   (Ph-N)

              AC Voltage Regulation (Batt. Mode): ± 1 %

              Frequency Range (Synchronized Range): 46~54Hz or 56~64Hz

              Frequency Range (Batt. Mode): 50/60 Hz ± 1%

              Harmonic Distortion:@ 1 % THD (Linear Load) ; @ 3 % THD (Non-linear Load)

              Waveform: Pure Sinewave

              Current Crest Ratio:3:1 (max.)

              Transfer Time: 0 for AC Mode to Batt. Mode, 0 for  for Inverter to Bypass

               Overload Capability:

100-110% for 60 min, 111-125% for 10 min, 126%~150% for 1 min; >150% or 400ms

Bypass

Nominal Voltage:3 x 380/400/415 VAC (3Ph+N)

Voltage Range: -30% ~ +20% (Adjustable)

Frequency Range(Synchronized Range):46~54Hz or 56~64Hz

Overload Capability:> 130% 1 minute (default) Continously working until breaker protection (optional)

 

Efficiency

              AC Mode: 96.0%

              Battery Mode: 96.0%

              ECO Mode: 99.0%

Battery

                Model 30000 (L)*

Standard Model

                Type: 12 V/7 Ah

                Total Battery Quantity: (16+16) pcs x 2 strings

                Typical Recharge Time: 9 hours recover to 90% capacity

                Charging Voltage: +/-218 VDC ± 10%

                Charging Current: 1A ~ 12A (Adjustable)

  Long-run Model.

                                     Type: Depending on application

                                     Total Battery Quantity:+/-16 pcs ~ +/- 20 pcs (Adjustable)

                                     Charging Voltage:+/-13.65V x N (N=16~20)

                                       Charging Current:1A ~ 12A (Adjustable)

 

 

Indicators

LCD Pane: UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

 

Physical

Standard Model:

              Dimension (W x H x D) (mm): 815 x 300 x 1000

              Net weight:225

Long-run Model:

               Dimension (W x H x D) (mm): 815 x 300 x 1000

              Net weight: 60

 

Environment

Operating temperature: 0-40°C

              Operating Humidity:< 95 % and non-condensing

              Altitude**:0 ~ 1500m at full load

              Noise Level: Less than 63 dB @1 Meter

 

Management

              Smart RS-232/USB: Supports Windows® Family, Linux and MAC

              Optional SNMP: Power management from SNMP manager and web browser

              

 

 

           

 

Note: All specifications are subject to change without notice

Reviews

There are no reviews yet.

Be the first to review “AMB-ON-PLUS-30000 (L)*”

Your email address will not be published. Required fields are marked *