Feature
  • True double-conversion
  • LCD screen auto-rotation with Rack position (only for 10K-40K models)
  • DSP technology guarantees high performance
  • Output power factor 1
  • Active power factor correction in all phases
  • 50Hz/60Hz frequency converter mode
  • ECO mode operation for energy saving (ECO)
  • Emergency power off function (EPO)
  • Generator compatible
  • Supports dual AC inputs
  • Adjustable battery numbers
  • Parallel operation with commom battery

Specification

 

MODEL        10KL       15KL       20KL         30KL        40KL        60KL
PHASE                3-phase in / 3-phase out, 3-phase in / 1-phase out, 1-phase in / 1-phase out,
CAPACITY 10KVA/10KW 15KVA/15KW 20KVA/20KW 30KVA/30KW 40KVA/40KW 60KVA/60KW
PARALLEL CAPABILITY                                                                                4
INPUT
Nominal Voltage                   3 x 380/400/415 VAC (3Ph+N+PE) or 208*/220/230/240 VAC (Ph+N+PE)
Voltage Range                     110-520 VAC (3-phase) @ 50% load ; 305-490 VAC (3-phase) @ 100% load
Frequency                                                                         40~70 Hz
Power Factor                                                                           ≧ 0.99  @ 100% load
Harmonic Distortion                                      ≦ 2 % THD (100% Linear Load) ; 5 % THD (Non-linear Load)
OUTPUT
Output Voltage  3 x 360*/380/400/415 VAC (3Ph+N+PE)  or        208*/220/230/240 VAC (Ph+N+PE) 3 x 360*/380/400/415 VAC (3Ph+N+PE)
AC Voltage Regulation (Batt. Mode)                                                                               ± 1%
Frequency Range (Synchronized Range)                                                                           50-60 Hz
Frequency Range (Batt. Mode)                                                       50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio                                                                           3:1 (max.)
Harmonic Distortion                                      ≦ 2 % THD (100% Linear Load) ; 5 % THD (Non-linear Load)
Transfer Time AC mode to Battery mode                                                                               Zero
Inverter to Bypass                                                                               Zero
Waveform (Batt. Mode)                                                                      Pure Sinewave
Overload AC Mode      100-110% for 60 min, 110-125% for 10 min, 125%~150% for 1 min; >150% immediately
Battery Mode      100-110% for 60 min, 110-125% for 10 min, 125%~150% for 1 min; >150% immediately
EFFICIENCY
AC Mode                                                                              95.5%
ECO Mode                                                                              98.5%
Battery Mode                                                                              94.5%
Short Circuit                                                                    Hold Whole System
BATTERY
Battery Type                                                          Depending on the applications
Battery Numbers    20 pcs                                    32~40 pcs (Adjustable)
Charging Current (max.)                                      1A~15A(Adjustable) 1A~16A
(Adjustable)
1A~18A
(Adjustable)
Charging Voltage +/- 13.65 VDC x N (N=10)                              +/- 13.65 VDC x N (N=16~20)
PHYSICAL
Dimension, D x W x H (mm)                                                      680 x 438 x 133 [3U] 797x438x176 [4U]
Net Weight (Kgs)           27            30             30              32            34           45
ENVIRONMENT
Operating Temperature                                                                              0-40°C
Operating Humidity                                                             < 95 % and non-condensing
Noise Level Less than 62dBA @ 1 Meter Less than 65dB @ 1 Meter Less than 65dB @ 1 Meter Less than 65dB @ 1 Meter Less than 70dB @ 1 Meter
MANAGEMENT
Smart RS-232/USB/RS-485/Parallel Port/REPO/Coupler                                                  Supports Windows® family, Linux and MAC
Optional SNMP                                      Power management from SNMP manager and web browser
STANDARDS
Safety                                                         IEC/EN 62040-1, IEC/EN 60950-1
EMI                                                                           IEC/EN 62040-2
EMC IEC/EN 62040-2, IEC/EN 61000-4-2, IEC/EN 61000-4-3, IEC/EN 61000-4-4,IEC/EN 61000-4-5, IEC/EN 61000-4-6, IEC/EN 61000-4-8, IEC/EN 61000-2-2

*When output voltage is set as 3 x 360VAC or 208 VAC, the output power of the unit will be de-rated to 90%. .
Product specifications are subject to change without further notice.