Model: AMB-ON-PLUS-6000-RT
Specification
Phase: Single phase with ground
Capacity:6000 VA / 6000 W
Input
Nominal Voltage: 208/220/230/240 VAC
Voltage range: 110~300VAC ± 3 % at 50% load
176~300VAC ± 3 % at 100% load
Frequency Range:46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz
Power Factor:≥ 0.99 @ full load
Harmonic Distortion (THDi): < 4% @100% Load, < 6% @50% Load
Output
Output Voltage(Batt. mode): 208*/220/230/240 VAC
AC Voltage Regulation (Batt. Mode): ± 1 %
Frequency Range (Synchronized Range): 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz
Frequency Range (Batt. Mode): 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Harmonic Distortion: ≤ 1 % THD (Linear Load) ; ≤ 4 % THD (Non-linear Load)
Waveform: Pure Sinewave
THDv: ≤ 3% @ linear load, ≤5%@non-linear load
Current Crest Ratio: 3:1 (max.)
Transfer Time: 0 for AC Mode to Batt. Mode, 0 for Inverter to Bypass
Efficiency
AC Mode: ≥ 94% @ full charged battery
Battery Mode: ≥ 92%
ECO Mode: ≥ 98.5% @ full charged battery
Battery
Model 6000L
Standard Model
Type: 12 V/ 9 Ah
Total Battery Quantity:16
Total Battery Quantity: 20
Recharge Time: 9 hours recover to 90% capacity for internal battery@ 2A charging current
Charging Voltage: 218.4 VDC ± 1%
Charging Voltage: 273 VDC ± 1%
Charging Current: 1.0 A
Long-run Model
Type: Depending on applications
Total Battery Quantity: 16-20**
Charging Voltage:(13.65VDC x battery number) ± 1%
Charging Current: 4.0 A
Indicators
LCD Display: UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault condition
Alarm:
Battery Mode: Sounding every 4 seconds
Low Battery: Sounding every second
Overload: Sounding twice every second
Fault: Continuously sounding
Physical
Standard Model
Dimension (W x H x D) (mm): UPS Unit: 610x438x88 [2U]
Battery Pack:715x438x88 [2U]
Net weight : UPS Unit: 17
Battery Pack: 48
Dimension (W x H x D) (mm): UPS Unit: 610x438x88 [2U]
Battery Pack:600x438x133 [3U]
Net weight : UPS Unit: 17
Battery Pack: 57
Environment
Operating Humidity: 20-90 % RH @ 0- 40°C (non-condensing)
Noise Level: Less than 55dB @ 1 Meter
Management
Smart RS-232/USB: Supports Windows ® 2000/2003/XP/Vista/2008/7/8/10, Linux and MAC
Optional SNMP: Power management from SNMP manager and web browser
Power Management Software: Yes
Standard
EMC/safety: EMC EN62040-2 C2 for CE models
Note: All specifications are subject to change without notice